PCI/Mass Storage Section Cooling
Six 92-mm fans located between the mass storage devices and the PCI card cage provide airflow through
these devices. The PCI fans are powered off of housekeeping power and run at full speed at all times. The air
is pulled through the mass storage devices and pushed through the PCI card cage. Separation is provided
between the PCI bulkheads to allow adequate exhaust ventilation and to help reduce the localized airflow
dead spots that typically occur at the faceplate tail of each PCI card.
Standby Cooling
Several components within the chassis consume significant amounts of power while the system is in standby
mode. The system fans will run at a portion of full speed during standby to remove the resulting heat from the
cabinet. The fans within the power supply will operate at full speed during standby.

Typical Power Dissipation and Cooling

Table B-5 provides calculations for configurations as described in the table.
Table B-5
Typical HP Integrity rx8620 Server Configurations
Memory
Cell
per Cell
Board
Board
Qty
GBytes
4
16
4
8
4
4
2
16
2
8
2
4
1
4
The air-conditioning data in Table B-5 is derived using the following equations.
Watts x (0.860) = kcal/hour
Watts x (3.414) = Btu/hour
BTU/hour divided by 12,000 = tons of refrigeration required
NOTE
When determining power requirements, you must consider any peripheral equipment that will
be installed during initial installation or as a later update. Refer to the applicable
documentation for such devices to determine the power and air-conditioning that is required to
support these devices.
Appendix B
PCI Cards
(assumes
DVDs
10W each)
Qty
Qty
16
2
16
2
8
0
16
2
8
0
8
0
8
0
Hard
Bulk
Core
Disk
Power
I/O
Drives
Supplies
Qty
Qty
Qty
4
2
6
4
2
6
2
2
6
4
2
4
2
2
4
2
2
4
1
1
3
System Specifications
Environmental Specifications
Typical
Typical
Power
Cooling
Watts
BTU/hour
3800
12973
3395
11591
3177
10846
2241
7651
1936
6610
1880
6418
1228
4192