2 Site preparation

For information on general computer room site preparation, see the HP Generalized Site Preparation
Guide on the HP website:
http://www.hp.com/go/Integrity_Servers-docs
IMPORTANT:
the temperature and humidity of the installation facility after removing the shipping materials. A
minimum of one hour per 10° C (50° F) of temperature difference between the shipping facility
and installation facility is required.

Server dimensions and weight

Table 3 Rack or pedestal-mounted server dimensions
Data center server dimensions
Depth
Width
Height
Weight
Rack unit

Grounding

The site building must provide a safety ground/protective earth for each AC service entrance to
all cabinets.
Install a PE conductor that is identical in size, insulation material, and thickness to the branch-circuit
supply conductors. The PE conductor must be green with yellow stripes. The earthing conductor is
to be connected from the unit to the building installation earth or, if supplied by a separately
derived system, at the supply transformer or motor-generator set grounding point.

Server electrical specifications

System power specifications

Available power (output) is the maximum DC power that the power supply can supply to the system.
Maximum input power is what the power supply requires from the AC line to deliver that maximum
DC output (given worst case efficiency and maximum loading).
Maximum input current is the worst case/highest current given the lowest input voltage and the
maximum input power.
Table 4 System power specifications
Input voltage
Input current (maximum)
Input frequency
Power supply maximum output power
14
Site preparation
To avoid hardware damage, allow the thermal mass of the product to equalize to
Dimensions and weight
Parameter
69.2 cm (27.25 in)
48.3 cm (19 in)
8.9 cm (3.5 in)
Maximum configuration – 30 kg (66 lb)
2U
100 V AC
1 10 - 120 V AC
9.3 A
9.5 A
47 to 63 Hz
47 to 53 Hz
800 W (MAX)
900 W (MAX)
+12V /66.7A MAX
+12V /75A MAX
Value
200 - 240 V AC
6.6 A
57 to 63 Hz
1200 W (MAX)
+12V /100A MAX
HP Confidential