Fig. 5 Rj45 Socket Front View; Fig. 6 Connection Diagram Rs485-Modbus 4W; Tab. 18 Pin Assignment Rs485 4W-Modbus To Rj45 Plug - KEB COMBIVERT S6 Instructions For Use Manual

Hide thumbs Also See for COMBIVERT S6:
Table of Contents

Advertisement

Connection X4B
8
1
Fig. 5: RJ45 socket front view
ma_dr_s6-cu-p-inst-20156056_en
max.line length
Connection cable (minimum require-
ment)
PIN
Signal
1
RxD-B
2
RxD-A
3
n.c.
4
TxD-A
5
TxD-B
6
n.c.
7
n.c.
8
GND
Housing
Shielding
Tab. 18: PIN assignment RS485 4W-Modbus to RJ45 plug
Master
Tx
Rx
Fig. 6: Connection diagram RS485-Modbus 4W
Fieldbus interfaces | 7
1200 m (depending on bus speed)
S/UTP (twisted pairs, shield connected
to PE on one side)
EIA/TIA-485 Name
Function
B'
Receive signal
A'
Received signal inverted
n.c.
reserved
A
Transmit signal inverted
B
Transmission signal
n.c.
reserved
n.c.
reserved
GND
Reference potential
Shielding
Shielding
COMBIVERT
Rx
Tx
33