Synchronous Communication Mode; Rs485 Potential-Free; Tab. 17 Error Status List - KEB COMBIVERT S6 Instructions For Use Manual

Hide thumbs Also See for COMBIVERT S6:
Table of Contents

Advertisement

7 | Fieldbus interfaces
Error status list
7.3.1 Synchronous communication mode
7.4 RS485 potential-free
Specification
32
Status
Light pattern
Local Error
r-0-0-0-0-0 (grid 200 ms)
Process Data or
r-0-r-0-0-0-0-0 (grid 200
EtherCAT Watchdog
ms)
Legend
r: Red
g: Green
0: off
Error
Communication or device
error
Process data watchdog
timeout
Local error
Invalid configuration
Loading error
Tab. 17: Error status list
The COMBIVERT with control board PRO supports a so-called synchronous com-
munication mode. This is titled differently for the different fieldbuses. In EtherCAT,
this functionality is managed under the term Distributed Clocks (DC).
Ultimately, the synchronous operating mode means that the internal interrupt grid
of the drive controller is synchronised to the synchronous signal generated by the
fieldbus.
The COMBIVERT with control board PRO does not support any values for the syn-
chronous cycle time. Which dependencies exist here and which parameters have
an influence can be found in the chapters "Switching frequency and derating" in the
programming manual.
Interface
Transmission speed
Bus nodes
Common-mode voltage range
Potential separation
Bus termination
Description
Local error; Device has inde-
pendently changed status from
OPERTIONAL to SAFE-OPER-
ATIONAL. Error bit is set to "1".
A watchdog error has occurred
in the application.
The red/green signals are shif-
ted by 180°. In case of overlap-
ping, red has priority.
Meaning
A communication or
device error has occurred.
The watchdog application
reports a timeout.
The fieldbus status has
changed due to an error.
General configuration er-
ror
Loading error during initial-
isation
RS485
4W
9.6, 19.2, 38.4, 55.5, 57.6, 100, 115.2,
125, 250, 500 kBit/s
2 (1:1 connection through fixed bus ter-
minating resistor)
0...12 V to the reference potential
Potential-free to the reference potential
(functional separation)
120 Ω each (pin 1 and 2; 4 and 5);
integrated (cannot be switched off)
ma_dr_s6-cu-p-inst-20156056_en
KEB Automation KG
Example
The device stops respond-
ing
Sync-Manager timeout
Device changes its
EtherCAT status from OP
to SafeOPError due to a
synchronisation error.
Change of status due to
register or object settings
that are not possible or in-
valid hardware configura-
tion.
Checksum error in the
flash memory of the ap-
plication controller.