Basic settings for the actuator controls
8.2.
Setting via hardware (switches) or via software
8.3.
Type of seating: set
26
The switch [S5] position determines whether the hardware settings (switches) or the
software settings (via AUMA CDT software) are currently active.
Figure 26: Switch [S5] = Hardware/software mode
Table 6:
Switch [S5] functions
OFF
Hardware mode (factory setting on delivery)
(1)
Settings of switches [S2] through [S4] and [S6] through [S10] are valid. The values
cannot be changed via AUMA CDT software.
ON
Software mode (sliding switch at white dot)
(0)
Settings of switches [S2] through [S4] and [S6] through [S10] are NOT relevant.
Settings are defined via software parameters.
Valve damage due to incorrect setting!
The type of seating setting (limit or torque seating) must match the selection for
the valve.
Only change the setting with prior consent of the valve manufacturer.
Setting via switches
Condition: Switch [S5] is in position OFF (hardware mode).
SV 05.1
with actuator controls MEC 03.1
SV 07.1