Grounding The Pv Inverter; Earth Fault Alarm - Q CELLS Q.VOLT-G2 HYB-4.6kW.1.1 Installation Manual

Hide thumbs Also See for Q.VOLT-G2 HYB-4.6kW.1.1:
Table of Contents

Advertisement

2.3.5 Grounding the PV INVERTER

DANGER
High touch current, earth connection essential before connecting supply
The PV INVERTER complies with the local requirements for grounding the PV INVERTER.
Q CELLS recommends connecting and grounding the PV INVERTER's frame and other electricity
conducting surfaces in such a way that there is continuous conduction in order to achieve maximum
protection for systems and persons. And the PV INVERTER's DC (+) pole and DC (-) pole are not
permitted to be grounded.
* Double Grounding Point
Q.HOME
ESS HYB-G2 must be connected to an additional ground on the enclosure.
+
The grounding method on the enclosure is as follows :
• Bolts : SJ60-00126A
• SCREW-MACHINE : PH, +, WSP, M4, L12, NTR, SUS304
• Torque for fastening bolts : 1.2 - 1.8 Nm
7-8 mm
10
6 mm
2
[ Figure 2-9 : Ring terminal (10R6-4) ]

2.4 Earth Fault Alarm

When an earth fault occurs, the inverter stops operation and notifies earth fault code to the installer and administrator.
Note: This feature is only supported on models released in Australia.
20
[ Figure 2-8 : Work on the ring terminal ]
10 mm
4 mm
[ Figure 2-10 : Double Grounding Point of
Q.HOME
ESS HYB-G2 ]
+
I
12
Safety