Mounting the operation panel (FR-DU07) on the enclosure surface

Having an operation panel or a parameter unit on the enclosure surface is convenient. With a connection cable, you
can mount the operation panel (FR-DU07) to the enclosure surface, and connect it to the inverter.
Use the option FR-CB2, or the following connector and cable available on the market.
Securely insert one end of connection cable into the PU connector of the inverter and the other end into the
connection connector of the operation panel (FR-DU07) along the guides until the stoppers are fixed.
Operation panel(FR-DU07)
REMARKS
· Refer to the following when fabricating the cable on the user side. Keep the total cable length within 20m (65.6 feet).
Commercially available product examples (as of Jan. 2010)
Product
1) Communication cable
2) RJ-45 connector
RS-485 terminal block
 Conforming standard: EIA-485(RS-485)
 Transmission format: Multidrop link
 Communication speed: MAX 38400bps
 Overall length: 500m (1640 feet)
 Connection cable:Twisted pair cable
(4 pairs)
2.3.6

Communication operation

Using the PU connector or RS-485 terminal, you can perform communication operation from a personal computer
etc. When the PU connector is connected with a personal, FA or other computer by a communication cable, a user
program can run and monitor the inverter or read and write to parameters.
For the Mitsubishi inverter protocol (computer link operation), communication can be performed with the PU
connector and RS-485 terminal.
For the Modbus-RTU protocol, communication can be performed with the RS-485 terminal.
For further details, refer to 335.
Parameter unit connection cable
(FR-CB2
)(option)
Operation panel connection connector
(FR-ADP)(option)
Type
SGLPEV-T (Cat5e/300m)
Mitsubishi Cable Industries, Ltd.
24AWG × 4P
5-554720-3
Tyco Electronics Corporation
Control circuit specifications
Maker
OPEN
Terminating resistor switch
Factory-set to "OPEN".
Set only the terminating resistor switch of
100Ω
the remotest inverter to the "100Ω" position.
RDA1
RDB1
RDA2
RDB2
(RXD1+)
(RXD1-)
(RXD2+)
(RXD2-)
SDA1
SDB1
SDA2
SDB2
TXD
(TXD1+)
(TXD1-)
(TXD2+)
(TXD2-)
P5S
SG
P5S
SG
(VCC)
(GND)
(VCC)
(GND)
RXD
VCC
2
33