 Connect the red voltage test lead to the "U1" terminal.
 Connect the yellow voltage test lead to the "U2" terminal.
 Connect the blue voltage test lead to the "U3" terminal.
 Connect the I1 current probe output plug to the "I1" jack.
 Connect the I2 current probe output plug to the "I2" jack.
 Connect the I3 current probe output plug to the "I3" jack.
4. Connect the voltage test leads and current probe to the electrical
equipment to be tested.
If possible, before connecting the voltage test leads and current probe
to the electrical equipment to be tested, take off the electrical
equipment's power.
 Connect the red voltage test alligator to the line "A".
 Connect the yellow voltage test alligator to the line "B".
 Connect the blue voltage test alligator to the line "C".
 Press I1 current probe trigger to open the jaw and fully enclose the Line
"A".
11
Press I2 current probe trigger to open the jaw and fully enclose the Line
"B".
12
Press I3 current probe trigger to open the jaw and fully enclose the Line
"C".
5. Press "POWER" key to select (P1, Q1, S1, PF1), (P2, Q2, S2, PF2),
(P3, Q3, S3, PF3) and (Pt, Qt, St, PFt) measured values.
6. Frequency (Hz), Phase Angle (Θ) and Power Factor (pF) measurement:
 Press "PFΘ" key to cycle shows the PF and Θ measured values.
 Press "Hz I4" key show the Hz measured value.
7. Voltage and Current THDR THDF measurement:
Please refer to section 4-1-12 "THD" key description.
8. Voltage and Current waveform harmonic measurement:
User Manual
CAUTION

Advertisement