3-4 Electrical Specification

❑ AC Voltage Trms measurement (V):
Range
Resolution
999.9V
0.1V
• Display item: RMS voltage value for each channel.
❑ AC Current Trms Measurement (A):
Range Resolution
999.9A
0.1A
• Display item: RMS current value for each channel.
❑ Active Power measurement P (KW):
Range
999.9KW
• Display items: Active power of each channel and its sum of multiple
• Polarity display: For influx (consumption) No symbol, For outflow
User Manual
Accuracy: ±(% of reading + number of digits) at 18°C to
28°C ( 64°C to 82°C) with relative humidity to 80%.
The current error is specified within the largest circle which
can be drawn inside the jaw.
Accuracy
(0.3% rdg
10dgts) (>10V)
Accuracy
(including current
probe)
(0.5%rdg15dgts)
(>10A)
Resolution
channels.
(regenerative) " - ".
Input
impedance
2MΩ
Current
probe
output
0.35mV/A 1000Arms
0.1KW
Overload
Nominal power
protection
system frequency
1000Vrms
45Hz ~ 66Hz
Overload
Nominal power
protection
system frequency
45Hz ~ 66Hz
Accuracy
1.0%rdg20dgts

Advertisement