Press key to cycle through the
Minimum reading for Active power ("P" mark is blinking) with its Q, S, V, A
reading and its PF, Θ, Hz, I4 reading by press "PFΘ" and "Hz I4" keys.
Minimum reading for Reactive power ("Q" mark is blinking) with its P, S,
V, A reading and its PF, Θ, Hz, I4 reading by press "PFΘ" and "Hz I4"
keys.
Minimum reading for Apparent power ("S" mark is blinking) with its P, Q,
V, A reading and its PF, Θ, Hz, I4 reading by press "PFΘ" and "Hz I4"
keys.
c). Current reading, the " REC " mark is displayed.
Press "MAX" key for 3 seconds to exit this mode.
11. PF Θkey: Display measured power factor or phase angle value control
key, the "PF" or "ψ" annunciator is displayed.
12. THD key: Display measured voltage or current THDF, THDR value
control key.
THDF: Total Harmonic Distortion of a waveform is compared to its
Fundamental.
THDR: Total Harmonic Distortion of a waveform is compared to the
waveforms rms value.
Press "THD" key to enter the Voltage U1, U2 and U3 THDR and THDF
measurement mode, the "THDR" and "THDF" marks are displayed.
Press "THD" key again to enter the Current I1, I2 and I3 measurement
mode, the "THDR" and "THDF" marks are displayed.
Press "THD" key again to exit this mode.
User Manual