Control Terminals

Connect the cables to the control terminals with a mating connector. Input and output
terminals have a functional isolation from terminal to terminal. They are connected to
the UPS through individual 1 MΩ resistors.
UPS
Connectors
(see Figure 73 on
page 107)
Figure 77. External Control Terminal Connections
NOTE If using a semiconductor switch type, pay attention to the proper polarity. A relay or other
mechanical control is preferred.

Relay Output Contacts

The UPS incorporates a programmable relay output with potential free contacts for
remote alarm indications (see Figure 73 on page 107). You can obtain an additional
four relay outputs with the X-Slot compatible Relay Interface Card.
The relay output contacts must not be connected to any utility connected circuits; the utility requires
reinforced insulation. The relay output contacts have a maximum rating of 30 Vac/1A and 60 Vdc/2A nominal
values.
Eaton BladeUPS (12 kVA) User's Guide
2
+ Polarity
Signal Input 1 (programmable)
1
– Polarity
2
+ Polarity
Signal Input 2 (programmable)
– Polarity
1
2
+ Polarity
Standalone/Parallel
1
– Polarity
2
REPO Normally Open
1
2
REPO Normally Closed
1
2
+ Polarity
Redundant Signal Wiring
– Polarity
1
(For Parallel Use Only)
3
Common
2
Normally Closed
1
Normally Open
W A R N I N G
S
164201649 Rev 6 www.eaton.com/powerqualtiy
COMMUNICATION
Relay Output