Eaton Powerware BladeUPS User Manual page 139

12 kva
Hide thumbs Also See for Powerware BladeUPS:
Table of Contents

Advertisement

Table 19. Electrical Output
Nominal Output Voltage
Output Voltage Variation
Connections
Short Circuit Capability
(Battery Mode)
Short Circuit Capability
(Normal Mode)
Nominal Output Frequency
Output Frequency Variation
Output Overload
Voltage Waveform
Full Output
BladeUPS 12 Model
120/208 Vac three-phase
104–132 Vac phase to neutral,
180–229 Vac phase to phase
IEC 309-60A power cord
For paralleling, a single Anderson input/output cord connects to the
BladeUPS Bar (see Table 14 on page 129).
84A, <300 ms
Limited by 50A input breaker
50–60 Hz auto-detection (Normal mode)
Synchronized (Normal mode)
±0.1 when not synchronized with source (Battery mode)
100–110%: load transfers to Bypass mode after 10 minutes
110–125%: load transfers to Bypass mode after 1 minute
125–150%: load transfers to Bypass mode after 5 seconds
>150%: load transfers to Bypass mode after 300 ms
Standard mode and Battery mode: Sine wave; <2% THD with linear load;
Eaton BladeUPS (12 kVA) User's Guide
230/400 Vac three-phase
207–253 Vac phase to neutral,
358–438 Vac phase to phase
IEC 309-32A power cord
Limited by 25A input breaker
50 or 60 Hz (Battery mode)
<5% with nonlinear load
Three-phase
S
164201649 Rev 6 www.eaton.com/powerqualtiy
SPECIFICATIONS
BladeUPS 12i Model
44A, <300 ms
131