3 Installation
!
20
3.3.3
Installing the Prosonic Flow W measuring sensors
(Clamp On)
1 or 3 traverses version
1.
Fix a tensioning band for small or large nominal diameters as described on
Page 17.
Install the second tensioning band (threaded bolt on the opposite side). The sec-
ond tensioning band must still be moveable.
Intermediate step:
You can obtain the sensor spacing using the Quick Setup menu "Sensor installation"
(see Page 60).
Note!
To run the "Sensor Installation" Quick Setup, the transmitter must be installed and con-
nected to the power supply.
2.
Enter the wire length on both halves of the wire.
Fig. 12:
Marking off of the determined cord length on the cord measurement equipment (SL = cord length)
3.
Push the cable lug and the fixer over the first threaded bolt. Lead each cord along
one side of the pipe. Push the cable lug and the fixer over the second threaded bolt.
Pull in the threaded bolt with the tensioning band until both cords are the same
length. Fix the tensioning band. Loosen the Phillips screws of the fixing parts.
Remove the cords.
Fig. 13:
Use of the cord measuring equipment for positioning of threaded bolts
SL
1
2
3
4
5
6
PROline Prosonic Flow 90
7
8
9
10
11