Output Terminal Function Selection (Pr. 190 To Pr. 192, Pr. 313 To Pr. 315) - Mitsubishi Electric FR-E720-0.1KNC Instruction Manual

Table of Contents

Advertisement

Function assignment of external terminals and CC-Link communication virtual terminals

5.13.3 Output terminal function selection (Pr. 190 to Pr. 192, Pr. 313 to Pr. 315)

The function assigned to the terminal Y0 or an output virtual terminal of CC-Link communication can be changed.
Parameter
Number
RX2 (terminal Y0)
190
∗1
function selection
191
RX6 function selection
∗1
192
RX7 function selection
∗1
313
RX9 function selection
314
RXA function selection
315
RXB function selection
∗1
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 197)
∗2
The setting values "93" and "193" are not available for Pr. 192.
∗3
The setting values "96" and "196" are only available for Pr. 190. When these values are set in Pr. 191, Pr. 192, and Pr. 313 to Pr. 315, their functions are
invalid.
(1)
Output signal list
A function can be assigned to the terminal Y0 or an output virtual terminal of CC-Link communication.
Refer to the following table and set the parameters: (0 to 99: positive logic, 100 to 199: negative logic)
Setting
Signal
Positive
Negative
logic
logic
0
100
RUN
Inverter running
1
101
SU
Up to frequency
3
103
OL
Overload alarm
Output frequency
4
104
FU
detection
Regenerative brake
7
107
RBP
pre-alarm
Electronic thermal O/L
8
108
THP
relay pre-alarm
Inverter operation
11
111
RY
ready
Output current
12
112
Y12
detection
13
113
Y13
Zero current detection
14
114
FDN
PID lower limit
15
115
FUP
PID upper limit
PID forward/reverse
16
116
RL
rotation output
20
120
BOF
Brake opening request
25
125
FAN
Fan fault output
Heatsink overheat
26
126
FIN
pre-alarm
During deceleration at
46
146
Y46
occurrence of power
failure
During PID control
47
147
PID
activated
Initial
Name
Value
Open collector
output terminal
9999
9999
9999
Function
Output during operation when the inverter output frequency
rises to or above Pr. 13 Starting frequency.
Output when the output frequency is reached to the set frequency. Pr. 41
Output while stall prevention function is activated.
Output when the output frequency reaches the frequency
set in Pr. 42 (Pr. 43 for reverse rotation).
Output when 85% of the regenerative brake duty set in Pr.
70 is reached.
Output when the electronic thermal value reaches 85% of
the trip level. (Electronic thermal relay function protection
(E.THT/E.THM) activates, when the value reached 100%.)
Output when reset process is completed (when the inverter
can be started by switching the start signal ON or while it is
running) after powering on inverter.
Output when the output current is higher than the Pr. 150
setting for longer than the time set in Pr. 151 .
Output when the output power is lower than the Pr. 152
setting for longer than the time set in Pr. 153 .
Output when the feedback value falls below the lower limit
of PID control.
Output when the feedback value rises above the upper limit
of PID control
Output when forward rotation is performed in PID control.
Output to open the brake when the brake sequence
function is selected.
Output at the time of a fan fault.
Output when the heatsink temperature reaches about 85%
of the heatsink overheat protection providing temperature.
Output when the power failure-time deceleration function is
executed.
(retained until release)
Output during PID control.
Initial Signal
0
RUN (inverter running)
FU (output frequency
4
detection)
99
ALM (fault output)
No function
No function
No function
Operation
Setting Range
0, 1, 3, 4, 7, 8, 11 to 16, 20, 25,
26, 46, 47, 64, 68, 80, 81, 90, 91,
93
, 95, 96
, 98, 99, 100, 101,
∗2
∗3
103, 104, 107, 108, 111 to 116,
120, 125, 126, 146, 147, 164,
168, 180, 181, 190, 191, 193
,
∗2
195, 196
, 198, 199, 9999
∗3
Refer
Related
to
Parameter
Page
169
171
Pr. 22, Pr. 23,
120
Pr. 66
Pr. 42, Pr. 43
171
Pr. 70
155
Pr. 9, Pr. 51
142
169
Pr. 150,
172
Pr. 151
Pr. 152,
172
Pr. 153
Pr. 127 to
203
Pr. 134
Pr. 278 to
Pr. 283,
160
Pr. 292
Pr. 244
213
239
Pr. 261
186
Pr. 127 to
203
Pr. 134
167
5