Misoperation prevention and parameter setting restriction
(3)
Registration of parameter to user group (Pr. 173)
When registering Pr. 3 to user group
1.
Confirm the operation display and operation
mode display.
The inverter should be at a stop.
Make sure that the inverter is in PU
operation mode.
2.
Press
to choose the parameter setting
mode.
3.
Turn
to change the set value to
"
".
4.
Press
to display
5.
Turn
until Pr. 3 appears.
6.
Press
to set.
"
" and "
To continue parameter registration, repeat
steps 3 to 6.
(4)
Deletion of parameter from user group (Pr. 174)
When deleting Pr. 3 from user group
1.
Confirm the operation display and operation
mode display.
The inverter should be at a stop.
The inverter should be in the PU operation
mode.
2.
Press
to choose the parameter setting
mode.
3.
Turn
until
4.
Press
to display "
5.
Turn
until Pr. 3 appears.
6.
Press
to set.
"
" and "
To continue parameter clear, repeat steps 3 to
6.
REMARKS
Pr. 77 and Pr. 160 can always be read, independently of the user group setting.
Pr. 77, Pr. 160 and Pr. 172 to Pr. 174 cannot be registered to the user group.
When Pr. 174 is read, "9999" is always displayed. Although "9999" can be written, no function is available.
When any value other than "9999" is set to Pr. 172, no function is available.
198
Operation
.
" are displayed alternately.
Operation
appears.
"
" are displayed alternately.
Flicker...Registration of Pr. 3 to user group
completed!!
Flicker...Clear of Pr. 3 to user group completed!!
Display
Parameter setting mode
Displays Pr. 173 User group
registration
When Pr. 173 is read, "9999"
is displayed
Select the parameter number
to be registered.
Display
Parameter setting mode
Displays Pr. 174 User group
clear
When Pr. 174 is read, "9999" is
displayed
Select the parameter number
to be registered.