Special operation and frequency control
(1)
Jog operation from operation panel
Selects Jog operation mode from the operation panel. Operation is performed only while the start button is pressed.
Operation
1.
Confirmation of the operating status indicator
and operation mode indicator
The monitor mode should have been
selected.
The inverter should be at a stop.
2.
Press
to choose the PU Jog operation
mode.
3.
Press
.
While
is pressed, the motor rotates.
The motor runs at 5Hz. (Pr. 15 initial value)
4.
Release
[When changing the frequency of PU Jog operation]
5.
Press
to choose the parameter setting
mode.
6.
Turn
until Pr. 15 Jog frequency appears.
7.
Press
to show the currently set value.
(5Hz)
8.
Turn
to set the value to "
(10Hz)
9.
Press
to set.
10.
Perform the operations in steps 1 to 4.
The motor rotates at 10Hz.
NOTE
When Pr. 29 Acceleration/deceleration pattern selection = "1" (S-pattern acceleration/deceleration A), the acceleration/
deceleration time is the period of time required to reach Pr. 3 Base frequency.
The Pr. 15 setting should be equal to or higher than the Pr. 13 Starting frequency.
During Jog operation, the second acceleration/deceleration via the RT signal cannot be selected. (The other second
functions are valid. (Refer to page 165))
Parameters referred to
Pr. 13 Starting frequency
Pr. 20 Acceleration/deceleration reference frequency, Pr. 21 Acceleration/deceleration time increments
Pr. 29 Acceleration/deceleration pattern selection
202
Hold down.
Release
".
Flicker...Parameter setting complete!!
Refer to page 138
Refer to page 139
Display
Stop
PRM indicator is lit.
(The parameter number read previously
appears.)
Refer to page 135