Frequency setting with input signals

5.9

Frequency setting with input signals

Purpose
To control the frequency with
combinations of input signals
To command smooth speed
transition with input signals
5.9.1

Operation by multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)

Use the virtual terminals of CC-Link communication to switch among the pre-set operation speeds set in parameters.
Any speed can be selected by simply turning ON/OFF the RH, RM, RL and REX signals.
Parameter
Number
Multi-speed setting (high
4
speed)
Multi-speed setting (middle
5
speed)
Multi-speed setting (low
6
speed)
24 ∗
Multi-speed setting (speed 4)
25 ∗
Multi-speed setting (speed 5)
26 ∗
Multi-speed setting (speed 6)
27 ∗
Multi-speed setting (speed 7)
232 ∗
Multi-speed setting (speed 8)
233 ∗
Multi-speed setting (speed 9)
234 ∗
Multi-speed setting (speed 10)
235 ∗
Multi-speed setting (speed 11)
236 ∗
Multi-speed setting (speed 12)
237 ∗
Multi-speed setting (speed 13)
238 ∗
Multi-speed setting (speed 14)
239 ∗
Multi-speed setting (speed 15)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
∗ This parameter can be set when Pr. 160 User group read selection = "0". (Refer to page 197)
Speed 1
(High speed)
Speed 2
(Middle speed)
ON
RH
ON
RM
RL
REMARKS
For multi-speed setting, if two or three speeds are simultaneously selected, priority is given to the set frequency of the lower
signal.
For example, when the RH and RM signals turn ON, the RM signal (Pr. 5) has a higher priority.
The RH, RM, RL signals are assigned to the virtual terminals of CC-Link communication in the initial setting. By setting "0 (RL)",
"1 (RM)", "2 (RH)" in Pr. 183 or Pr. 184 (input terminal function selection), you can assign the signals to other virtual terminals.
130
Multi-speed operation
Remote setting function
Name
Initial Value
60Hz
30Hz
10Hz
(1)
The inverter operates at frequencies set in Pr. 4 when RH signal is ON,
Pr. 5 when RM signal is ON and Pr. 6 when RL signal is ON.
Speed 3
(Low speed)
Time
ON
Parameter that should be Set
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Setting Range
0 to 400Hz
0 to 400Hz
0 to 400Hz
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
Multi speed setting for 3 speeds (Pr. 4 to Pr. 6)
Refer to Page
Pr. 59
Description
Frequency when RH turns ON
Frequency when RM turns ON
Frequency when RL turns ON
Frequency from 4 speed to 15 speed can
be set according to the combination of
the RH, RM, RL and REX signals.
9999: not selected
130
132