Operation via CC-Link communication and its settings
5.4.3

CC-Link communication reset selection (Pr.349)

The RY1A error reset command (on
disabled.
Parameter
Number
Communication
349
reset selection
(1)
Operation conditions of inverter reset
The following table shows the availability of the inverter reset in each operation mode.
Reset via CC-Link
communication
Switch OFF inverter power
Reset from the operation panel (Reset at inverter fault)
∗1 Inverter reset can be made any time.
∗2 Reset can be made only when the protective function of the inverter is activated.
REMARKS
• Refer to page 73 for the programming example of an inverter reset.
NOTE
When a communication line error has occurred, reset cannot be made from the network.
Communication continues during inverter reset. (The inverter cannot be controlled for about 1s after release of a
reset command.)
5.4.4

Communication EEPROM write selection (Pr. 342)

Storage device can be changed to RAM only from EEPROM+RAM for the parameter settings written through the CC-
Link communication. Use this function if parameter settings are changed frequently.
Parameter
Number
Communication EEPROM
342
write selection
The above parameters can be set when Pr. 160 User group read selection = "0." (Refer to page 197)
When changing the parameter values frequently, set "1" in Pr. 342 to write them to the RAM.
Performing frequent parameter write with "0 (initial value)" (EEPROM write) set will shorten the life of the EEPROM.
REMARKS
• When "1" (write to RAM only) is set in Pr. 342, powering OFF the inverter will erase the changed parameter values. Therefore,
the parameter values available when power is switched ON again are the values stored in EEPROM previously.
110
60) transmitted via CC-Link communication in PU operation mode can be
page
Initial
Name
Value
0
Resetting Method
Inverter reset (Refer to page 65)
Error reset (RY1A) at inverter fault
(Refer to page 60)
∗2
Initial
Name
Value
0
Setting
Range
0
Error reset is enabled independently of operation mode
1
Error reset is enabled only in the Network operation mode
∗1
Pr.349 = 0
Pr.349 = 1
∗2
Setting
Range
Parameter values written via CC-Link communication are
0
written to the EEPROM and RAM.
Parameter values written via CC-Link communication are
1
written to the RAM.
Function
Operation Mode
Network
PU Operation
Operation
Allowed
Disallowed
Allowed
Allowed
Allowed
Disallowed
Allowed
Allowed
Allowed
Allowed
Description