Installation Instructions
1

Panic and Fire Rated Devices

A .
Checklist
1. Check device for shipping damage prior to installation and make sure all parts are on hand.
2. Identify options provided with device.
3. Identify model, type and hand of trim if applicable (see exit device and trim instructions for reversing
hands).
4. Contact hardware supplier if device is damaged or missing parts.
B .
Required Components (Numbered list correlates with numbers in Figure 1)
1. Delayed Egress Exit Device
2. 24VDC UL Listed Regulated and Filtered Power Supply with Fire Alarm Interface (recommend
Securitron BPS 24-1 or 24-2 (UL294 Listed), depending on requirements). Power supply is NOT to
be used in UL603 Burglar Alarm System.
3. Power transfer UL or Ulc listed (2-10 wire depending on system)-Securitron (EPT) or equivalent.
4. Sign (MUST BE INSTALLED ON DOOR ABOVE DEVICE).
NOTE: The delayed egress system is to be installed in accordance with NFPA 101.
C .
Optional Components (Numbered list correlates with numbers in Figure 1)
5. Remote Annunciator
6. Door Position Switch (DPS)
7. Standard Trim
8. Electrified Trim
9. Device and Trim Cylinder
D .
Electrical Specifications*
Input Voltage 24VDC (+/-10%)
Wire Size:
18 AWG Min (up to 100')
Signal or Control 22AWG Min
Power Consumption:
Standard Device - 500mA
Device with Electric Trim - 883mA
*Follow Local Electrical Codes for Wiring.
NOTE: Components shown do not reflect all possible applications.
Consult manufacturer for special applications.
For installation assistance contact Corbin Russwin
1-800-543-3658 • techsupport.corbinrusswin@assaabloy.com
Copyright © 2018, ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or
in part without the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
6.
4.
PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE
OPENED IN 15 SECONDS.
7.
8.
Or
1.
9.
3
115 VAC
800 mA
2.
60 Hz
Fire
Alarm
Circuit
Req'd
5.
3.
Figure 1
FM209 10/18