Sungrow SG8.0RS User Manual page 98

1-phase pv grid-connected inverter
Hide thumbs Also See for SG8.0RS:
Table of Contents

Advertisement

7 iSolarCloud App
table 7-5 Description of Active Power Regulation Parameters
Parameter
Active Power Soft Start
after Fault
Active Power Soft Start
Time after Fault
Active Power Gradient
Control
Active Power Decline
Gradient
Active Power Rising
Gradient
Active Power Setting
Persistence
Active Power Limit
Active Power Limit
Ratio
Reactive Power Regulation
Tap Settings→Power Regulation Parameters→Reactive Power Regulation to enter the
screen, as shown in the following figure.
88
figure 7-16 Active Power Regulation
Description
Switch for activating/deactivating the function
of active power soft start after a fault occurs
The soft start time required for raising active
power from 0 to rated value after a fault occurs
Set whether to enable active power gradient
control
Decline gradient of inverter active power per
minute
Rising gradient of inverter active power per
minute
Switch for activating/deactivating the function
of active power setting persistence
Switch for limiting active power
The ratio of active power limit to rated power in
percentage
User Manual
Range
On/Off
1 s–1200 s
On/Off
1 %/min–
6000 %/min
1 %/min–
6000 %/min
On/Off
On/Off
0.0 %–
100.0 %