5 Electrical Connection
The following requirements about PV string connection must be met. Otherwise, it
may cause irreversible damage to the inverter, which is not covered by the
warranty.
Mixed use of PV modules of different brands or models in one MPPT circuit, or
PV modules of different orientation or inclination in a string may not damage in-
verter, but will cause system bad performance!
The inverter enters standby state when the input voltage ranges between 560 V
and 600 V. The inverter returns to running state once the voltage returns to the
MPPT operating voltage range, namely, 40 V to 560 V.
Note the following items when laying out cables on site:
The axial tension on PV connectors must not exceed 80 N. Avoid axial cable
stress on the connector for a long time during field wiring.
Radial stress or torque must not be generated on PV connectors. It may cause
the connector waterproof failure and reduce connector reliability.
Leave at least 50 mm of slack to avoid the external force generated by the cable
bending affecting the waterproof performance.
Refer to the specifications provided by the cable manufacturer for the minimum
cable bending radius. If the required bending radius is less than 50 mm, reserve
a bending radius of 50 mm. If the required bending radius is greater than 50 mm,
reserve the required minimum bending radius during wiring.

5.6.1 PV Input Configuration

The inverters SG5.0RS-ADA/SG8.0RS/SG9.0RS/SG10RS have three PV inputs, each
with independent MPP tracker. Each DC input area can operate independently.
The PV strings to each DC input may differ from each other, including PV module type,
number of PV modules in each string, angle of tilt, and installation orientation.
42