6 Commissioning
6.8
Single-phase Wireless Meter Networking Procedure (for
SG5.0RS-ADA)
Step 1 Press and hold the function button on WiNet-S2 for 5 – 10 s, and release it after the
RUN indicator turns to fast blinking in green. The WiNet-S2 is in networking mode.
Step 2 Press and hold the function button on WiMeter-S for 5 — 10 s, and release it after
the RUN indicator turns to fast blinking in green. The WiMeter-S is in networking mode.
Step 3 Check whether the WiMeter is online.
Log in to iSolarCloud App, select the corresponding plant, and check whether the S/N of "-
Networking Devices" displayed on the "Device" page is consistent with the S/N of the
WiMeter that is manually networked. If it is the same, the WiMeter-S is successfully online.
Step 4 If the WiMeter goes online in step 3, the networking is successful. If the WiMeter
does not come online within 5 minutes, repeat step 1 and 2.
74
User Manual