step 3 Apply paint to the grounding terminal to ensure corrosion resistance.
- - End
5.5

AC Cable Connection

5.5.1 AC Side Requirements

Only with the permission of the local grid department, the inverter can be con-
nected to the grid.
Before connecting the inverter to the grid, ensure the grid voltage and frequency comply with
requirements, for which, refer to "Technical Date". Otherwise, contact the electric power
company for help.
AC Circuit Breaker
An independent two-pole circuit breaker must be installed on the output side of the inverter
to ensure safe disconnection from the grid. The recommended specifications are as follows.
Inverter Model
SG5.0RS-ADA
SG8.0RS/SG9.0RS
SG10RS
Testing to AS/NNZS 4777.2:2020 Section for multiple phase combinations has not
been conducted.
Recommended Specification
32 A
50A
63 A
5 Electrical Connection
37