Prior to connecting the inverter to PV inputs, the specifications in the following table should
be met:
Inverter Model
All models
5.6.2 Assembling the PV Connectors
High voltage may be present in the inverter!
•
Ensure all cables are voltage-free before performing electrical operations.
•
Do not connect the DC switch and AC circuit breaker before finishing electrical
connection.
To ensure IP65 protection, use only the supplied connector.
step 1 Strip the insulation from each DC cable by 7 mm–8 mm.
step 2 Assemble the cable ends with the crimping pliers.
figure 5-3 PV Input Configuration
Open-circuit Voltage Limit
600 V
5 Electrical Connection
Max. current for input connector
20 A