6 Maintenance
6.2

Standard inspection and maintenance operations

6.3

Check the hydraulic pressure

6.4

Cleaning the casing

32
MIV-S V200
To guarantee optimum performance.
To extend the life of the equipment.
To provide an installation which offers the user optimum comfort over
time.
Caution
Only qualified professionals are authorised to carry out
maintenance work on the heat pump and the heating system.
Danger of electric shock
Before any work, switch off the power supply to the heat pump
and the backup boiler or the electric heating element, if present.
Caution
Before working on the refrigeration circuit, switch off the appliance
and wait a few minutes. Certain items of equipment such as the
compressor and the pipes can reach temperatures in excess of
100°C and high pressures, which may cause serious injuries.
Caution
Do not drain the installation, except in cases of absolute
necessity. E.g.: several months' absence with the risk of
temperatures in the building falling below freezing.
Important
Maintenance shall be performed only as recommended by the
manufacturer.
Replace any damaged component.
When breaking into the refrigerant circuit to make repairs – or
for any other purpose – remove the refrigerant. Recover the
refrigerant into the correct recovery cylinders.
An annual inspection with tightness check is obligatory. Schedule a
service by a qualified professional at a cold time of the year to check the
following points:
1. Operation of the installation.
2. Thermal output, by measuring the difference in temperature between
heating flow and return.
3. The setting for the safety thermostats.
1. Checking the hydraulic pressure in the installation.
2. If the hydraulic pressure is less than 0.08 MPa (0.8 bar), top up the
level of water in the heating installation so that the hydraulic pressure
is between 0.15 and 0.2 MPa (1.5 and 2.0 bar).
3. Carry out a visual check for any water leaks.
1. Clean the outside of the appliance using a damp cloth and a mild
detergent.
7748661 - v04 - 01022022