1MRS758755 C
For example, six setting groups can be controlled with three binary inputs. The
operation mode is set to "Logic mode 2" and inputs BI_SG_2 and BI_SG_5 are
connected together the same way as inputs BI_SG_3 and BI_SG_6.
Table 36: SG operation mode = "Logic mode 1"
BI_SG_2
Table 37: SG operation mode = "Logic mode 2"
BI_SG_2
The setting group 1 can be copied to any other or all groups from HMI (Copy group
1).
3.7

Test mode

3.7.1

Function blocks

REC615 & RER615
Technical Manual
time of installation and commissioning and not change it throughout the
protection relay's service. Changing the
"Logic mode 1" to "Logic mode 2" or from "Logic mode 2" to "Logic mode
1" does not affect the setting group (SG).
BI_SG_3
FALSE
FALSE
TRUE
FALSE
any
TRUE
any
any
any
any
any
any
BI_SG_3
FALSE
FALSE
TRUE
FALSE
any
TRUE
any
any
any
any
any
any
SG operation mode setting from
Input
BI_SG_4
BI_SG_5
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
TRUE
FALSE
any
TRUE
any
any
Input
BI_SG_4
BI_SG_5
FALSE
any
FALSE
any
FALSE
any
TRUE
FALSE
TRUE
TRUE
TRUE
any
Basic functions
SG
BI_SG_6
Active group
FALSE
1
FALSE
2
FALSE
3
FALSE
4
FALSE
5
TRUE
6
BI_SG_6
Active group
any
1
any
2
any
3
FALSE
4
FALSE
5
TRUE
6
75