Monitored Data; Technical Data; Technical Revision History - ABB RELION REC615 Technical Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

Protection related functions
Parameter
Values (Range)
2=Without Check
3=Current check
Retrip time
0...60000
CB failure delay
0...60000
Table 521: CCBRBRF Non group settings (Advanced)
Parameter
Values (Range)
CB fault delay
0...60000
Measurement
2=DFT
mode
3=Peak-to-Peak
Trip pulse time
0...60000
Start latching
1=Rising edge
mode
2=Level sensitive
5.2.8

Monitored data

5.2.8.1
Table 522: CCBRBRF Monitored data
Name
CCBRBRF
5.2.9

Technical data

Table 523: CCBRBRF Technical data
Characteristic
Operation accuracy
Operate time accuracy
Reset time
Retardation time
490
Unit
Step
ms
10
ms
10
Unit
Step
ms
10
ms
10
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the measured current: f
Hz
±1.5 % of the set value or ±0.002 × I
±1.0 % of the set value or ±20 ms
Typically 40 ms
<20 ms
1MRS758755 C
Default
Description
120
Delay timer for ret-
rip
240
Delay timer for
backup trip
Default
Description
5000
Circuit breaker faul-
ty delay
3=Peak-to-Peak
Phase current
measurement
mode of function
200
Pulse length of ret-
rip and backup trip
outputs
1=Rising edge
Start reset delayed
or immediately
Unit
Description
Status
n
REC615 & RER615
Technical Manual
±2
n