Application; Signals - ABB RELION REC615 Technical Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

1MRS758755 C
increased or decreased depending on the sign and value of the
setting.
Timer
Once activated, the timer activates the START output. The time characteristic is
according to DT. When the operation timer has reached the value set by
delay time , the OPERATE output is activated. If the starting condition disappears
before the module operates, the reset timer is activated. If the reset timer reaches
the value set by
is deactivated.
The timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operation time. The value is
available in the monitored data view.
Blocking logic
There are three operation modes in the blocking function. The operation modes
are controlled by the BLOCK input and the global setting in Configuration >
System > Blocking mode which selects the blocking mode. The BLOCK input can
be controlled by a binary input, a horizontal communication input or an internal
signal of the protection relay's program. The influence of the BLOCK signal activation
is preselected with the global setting
The
mode, the operation timer is frozen to the prevailing value, but the OPERATE output
is not deactivated when blocking is activated. In the "Block all" mode, the whole
function is blocked and the timers are reset. In the "Block OPERATE output" mode,
the function operates normally but the OPERATE output is not activated.
4.7.5

Application

The function block can be used for any general analog signal protection, either
underprotection or overprotection. The setting range is wide, allowing various
protection schemes for the function. Thus, the absolute hysteresis can be set to
a value that suits the application.
The temperature protection using the RTD sensors can be done using the function
block. The measured temperature can be fed from the RTD sensor to the function
input that detects too high temperatures in the motor bearings or windings, for
example. When the ENA_ADD input is enabled, the threshold value of the internal
comparator is the sum of the
temporal increase or decrease of the level detector depending on the sign and value
of the
If, for example,
active, the input signal needs to rise above 120 before MAPGAPC operates.
REC615 & RER615
Technical Manual
Reset delay time , the operation timer resets and the START output
Blocking mode setting has three blocking methods. In the "Freeze timers"
Start value Add setting, for example, when the emergency start is activated.
Start value is 100, Start value Add is 20 and the ENA_ADD input is
Blocking mode .
Start value Add and Start value settings. This allows a
Protection functions
Start value Add
Operate
473