Binary Input; Binary Input Filter Time - ABB RELION REC615 Technical Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

1MRS758755 C
Table 49: Maximum current protection setting values
Application nominal
current (I
...1250
1250...2500
2500...4000
Voltage sensor setting example
The voltage sensor is based on the resistive divider or capacitive divider
principle. Therefore, the voltage is linear throughout the whole measuring
range. The output signal is a voltage, directly proportional to the primary
voltage. For the voltage sensor all parameters are readable directly from its
rating plate and conversions are not needed.
In this example the system phase-to-phase voltage rating is 10 kV. Thus,
the
sensor measurement support the
sensor" and it cannot be changed. The same applies for the
parameter which is always set to "WYE" type. The division ratio for ABB
voltage sensors is most often 10000:1. Thus, the
usually set to "10000". The primary voltage is proportionally divided by this
division ratio.
Table 50: Example setting values for voltage sensor
Setting
Primary voltage
VT connection
Voltage input type
Division ratio
3.11

Binary input

3.11.1

Binary input filter time

The filter time eliminates debounces and short disturbances on a binary input. The
filter time is set for each binary input of the protection relay.
REC615 & RER615
Technical Manual
)
n
Primary voltage parameter is set to 10 kV. For protection relays with
Rated secondary value
with 80A / 0.150 V at 50
Hz
A 1.000...46.875 mV/Hz
A 46.875...93.750 mV/Hz
A 93.750...150.000 mV/Hz
Voltage input type is always set to "CVD
Value
10 kV
Wye
3=CVD sensor
10000
Basic functions
Current protection
maximum setting value
not to be exceeded
40 × I
(Also the maximum
n
of the start value setting
range)
20 × I
n
12.5 × I
n
VT connection
Division ratio parameter is
91

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer615

Table of Contents