Settings; Monitored Data; Technical Revision History - ABB RELION REC615 Technical Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

1MRS758755 C
5.3.6.2
TRPPTRC Output signals
Table 527: TRPPTRC Output signals
Name
TRIP
CL_LKOUT
5.3.7

Settings

5.3.7.1
TRPPTRC Non group settings (Basic)
Table 528: TRPPTRC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Trip pulse time
20...60000
Trip output mode
1=Non-latched
2=Latched
3=Lockout
5.3.8

Monitored data

5.3.8.1
TRPPTRC Monitored data
Table 529: TRPPTRC Monitored data
Name
TRPPTRC
REC615 & RER615
Technical Manual
Type
BOOLEAN
BOOLEAN
Unit
Step
ms
1
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Protection related functions
Description
General trip output signal
Circuit breaker lockout out-
put (set until reset)
Default
Description
1=on
Operation Off / On
250
Minimum duration
of trip output sig-
nal
1=Non-latched
Select the opera-
tion mode for trip
output
Unit
Description
Status
495

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer615