Monitored Data - ABB RELION REC615 Technical Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

Basic functions
Parameter
Values (Range)
Val high high limit
-10000.0...10000.0
Value high limit
-10000.0...10000.0
Value low limit
-10000.0...10000.0
Value low low limit
-10000.0...10000.0
Value deadband
100...100000
3.13.5

Monitored data

Table 62: Monitored data
Name
Type
AI_DB1
FLOAT32
AI_RANGE1
Enum
AI_DB2
FLOAT32
AI_RANGE2
Enum
AI_DB3
FLOAT32
AI_RANGE3
Enum
AI_DB4
FLOAT32
AI_RANGE4
Enum
Table continues on the next page
112
Unit
Step
1
1
1
1
1
Values (Range)
Unit
-10000.0...10000 .0
0=normal
1=high
2=low
3=high-high
4=low-low
-10000.0...10000 .0
0=normal
1=high
2=low
3=high-high
4=low-low
-10000.0...10000 .0
0=normal
1=high
2=low
3=high-high
4=low-low
-10000.0...10000 .0
0=normal
1=high
2=low
3=high-high
4=low-low
1MRS758755 C
Default
Description
10000
Output value high
alarm limit for su-
pervision
10000
Output value high
warning limit for
supervision
-10000
Output value low
warning limit for
supervision
-10000
Output value low
alarm limit for su-
pervision
1000
Deadband configu-
ration value for in-
tegral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Description
mA input, Connectors 1-2, reported value
mA input, Connectors 1-2, range
mA input, Connectors 3-4, reported value
mA input, Connectors 3-4, range
RTD input, Connectors 5-6-11c, reported
value
RTD input, Connectors 5-6-11c, range
RTD input, Connectors 7-8-11c, reported
value
RTD input, Connectors 7-8-11c, range
REC615 & RER615
Technical Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer615

Table of Contents