Basic functions
Figure 109: Load profile record file naming
3.19.2.4
Clearing of record
The load profile record can be cleared with
communication or the ACT input in PCM600. Clearing of the record is allowed only
on the engineer and administrator authorization levels.
The load profile record is automatically cleared if the quantity selection parameters
are changed or any other parameter which affects the content of the COMTRADE
configuration file is changed. Also, if data source for selected quantity is removed,
for example, with ACT, the load profile recorder stops recording and previously
collected data are cleared.
3.19.3

Configuration

The load profile record can be configured with the PCM600 tool or any tool
supporting the IEC 61850 standard.
The load profile record can be enabled or disabled with the
the Configuration/Load Profile Record menu.
Each protection relay can be mapped to each of the quantity channels of the load
profile record. The mapping is done with the
corresponding quantity channel.
The memory consumption of load profile record is supervised, and indicated
with two signals MEM_WARN and MEM_ALARM, which could be used to notify the
customer that recording should be backlogged by reading the recorded data from
194
192 . 168 .
10
0 A
0 A
The IP number of the protection relay and the content of the
name setting are both included in the COMTRADE configuration file for
identification purposes.
.
187
L D P 1
B B
L D P 1 . C F G
B B
L D P 1 . D A T
Reset load profile rec via HMI,
Quantity selection setting of the
1MRS758755 C
Operation setting under
Bay
REC615 & RER615
Technical Manual