Basic functions
3.1.16

DNP3 settings

Table 23: DNP3 settings
Parameter
Values (Range)
Operation
1=on
5=off
Port
1=COM 1
2=COM 2
3=Ethernet - TCP 1
4=Ethernet TCP +UDP 1
Unit address
1...65519
Master address
1...65519
Mapping select
1...2
ClientIP
TCP port
20000...65535
TCP write authority
0=No clients
1=Reg. clients
2=All clients
Link keep-alive
0...65535
Validate master addr 1=Disable
2=Enable
Self address
1=Disable
2=Enable
Need time interval
0...65535
Time format
0=UTC
1=Local
CROB select timeout 1...65535
Data link confirm
0=Never
1=Only Multiframe
2=Always
Data link confirm TO
100...65535
Data link retries
0...65535
Data link Rx to Tx de-
0...255
lay
Data link inter char
0...20
delay
Data link frame
50...292
length
Table continues on the next page
54
Unit
Step
Default
5=off
3=Ethernet - TCP 1
1
1
1
3
1
1
0.0.0.0
1
20000
2=All clients
s
1
0
1=Disable
2=Enable
min
1
30
1=Local
s
1
10
0=Never
ms
1
3000
1
3
ms
1
0
char
1
4
bytes
1
292
1MRS758755 C
Description
Operation Off / On
Communication interface
selection
DNP unit address
DNP master and UR ad-
dress
Mapping select
IP address of client
TCP Port used on ether-
net communication
0=no client controls
allowed; 1=Controls al-
lowed by registered cli-
ents; 2=Controls allowed
by all clients
Link keep-alive interval
for DNP
Validate master address
on receive
Support self address
query function
Period to set IIN need
time bit
UTC or local. Coordinate
with master.
Control Relay Output
Block select timeout
Data link confirm mode
Data link confirm time-
out
Data link retries count
Turnaround transmission
delay
Inter character delay for
incoming messages
Data link maximum
frame length
REC615 & RER615
Technical Manual

Advertisement

Table of Contents