Ethernet Channel Supervision Schlcch - ABB RELION REC615 Technical Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

1MRS758755 C
Parameter
LNKLIV
REDLNKLIV
3.20.1.4
Settings
Redundancy settings
Table 217: Redundancy settings
Parameter
Redundant
mode
3.20.1.5
Monitored data
Monitored data is available in four locations.
• Monitoring > Communication > Ethernet > Activity > CHLIV_A
• Monitoring > Communication/ > Ethernet > Activity > REDCHLIV_B
• Monitoring > Communication > Ethernet > Link statuses > LNKLIV_A
• Monitoring > Communication > Ethernet > Link statuses > REDLNKLIV_B
3.20.2

Ethernet channel supervision SCHLCCH

3.20.2.1
Function block
Figure 111: Function block
3.20.2.2
Functionality
Ethernet channel supervision SCHLCCH represents X1/LAN, X2/LAN and X3/LAN
Ethernet channels.
An unused Ethernet port can be set "Off" with the setting Configuration >
Communication > Ethernet > Rear port(s) > Port x Mode. This setting closes the
REC615 & RER615
Technical Manual
Values
Unit
Step
(Range)
Up
Down
Up
Down
Values
Unit
Step
(Range)
None
PRP
HSR
Defaul
Description
t
Link status of redundant port LAN
A. Valid only when
is set to "HSR" or "PRP".
Link status of redundant port LAN
B. Valid only when
is set to "HSR" or "PRP".
Defaul
Description
t
None
Mode selection for Ethernet switch
on redundant communication mod-
ules. The "None" mode is used with
normal and Self-healing Ethernet
topologies.
Basic functions
Redundant mode
Redundant mode
211