3. Commissioning

Only trained specialist personnel may carry out start-up of the operating unit / actuator combination
JSD-TD25P-xxxxxx.
3.1.

Functional test

In case of first commissioning after installation, a functional test based on the application case must be
carried out in accordance with current guidelines for the application and their harmonized standards.
Note on functional test according to DIN EN ISO 13851:2019
This functional test is then carried out if the control unit / actuator combination JSD TD25P-
xxxxxx/JSTD25P-1 is operated as two-hand control unit in accordance with DIN EN ISO
13851:2019.
The activation of the safety outputs on the evaluation unit assumes the simultaneity of four input
signals of the two-hand control unit.
In order to set these signals, you must press in all four buttons on the Safeballs actuator within
0.5 sec.
The following table shows the switching of the safety outputs, depending on the inputs.
Push button
1
X
-
-
-
X
X
X
-
-
-
X
X
X
-
X
Created on: 10/02/2022
J.Fenner
File location:
ABB STOTZ-KONTAKT GmbH
Original operating manual for portable
operating unit with two-hand operation
with the name JSD-TD25P-xxxxxx and JSTD25P-1
Push button
2
-
X
-
-
X
-
-
X
X
-
X
X
-
X
Simultaneous actuation, within 0.5 sec.
X
Checked on: 11/02/2022
J.Marschall
Doc. name: Version 1.0
Push button
Push button
3
4
-
-
-
-
X
-
-
X
-
-
X
-
-
X
X
-
-
X
X
X
X
-
-
X
X
X
X
X
X
X
Change date: 28.02.24
Page 11 of 18
Safety outputs
-
-
-
-
-
-
-
-
-
-
-
-
-
-
X
Released on: 11/02/2022
J.Marschall