Protection related functions
Table 514: INRPHAR Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
5.1.8

Monitored data

5.1.8.1
INRPHAR Monitored data
Table 515: INRPHAR Monitored data
Name
INRPHAR
5.1.9

Technical data

Table 516: INRPHAR Technical data
Characteristic
Operation accuracy
Reset time
Reset ratio
Operate time accuracy
5.1.10

Technical revision history

Table 517: INRPHAR Technical revision history
Technical revision
B
C
480
Unit
Step
ms
1
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
At the frequency f = f
Current measurement:
±1.5 % of the set value or ±0.002 × I
Ratio I2f/I1f measurement:
±5.0 % of the set value
+35 ms / -0 ms
Typically 0.96
+35 ms / -0 ms
Default
20
Unit
n
n
Change
Internal improvement
Internal improvement
1MRS758755 C
Description
Reset delay time
Description
Status
REC615 & RER615
Technical Manual