Self-Supervision; Internal Faults - ABB RELION REC615 Technical Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

1MRS758755 C
Table 24: COM1/2 serial communication settings
Parameter
Values (Range)
Fiber mode
0=No fiber
2=Fiber optic
Serial mode
1=RS485 2Wire
2=RS485 4Wire
3=RS232 no hand-
shake
4=RS232 with hand-
shake
CTS delay
0...60000
RTS delay
0...60000
Baudrate
1=300
2=600
3=1200
4=2400
5=4800
6=9600
7=19200
8=38400
9=57600
10=115200
3.2

Self-supervision

The protection relay's extensive self-supervision system continuously supervises the
software and the electronics. It handles run-time fault situation and informs the
user about a fault via the LHMI and through the communication channels.
There are two types of fault indications.

• Internal faults

• Warnings
3.2.1
Internal faults
When an internal relay fault is detected, relay protection operation is disabled,
the green Ready LED begins to flash and the self-supervision output contact is
activated.
An indication about the fault is shown as a message on the LHMI. The text
Internal Fault with an additional text message, a code, date and time, is shown
to indicate the fault type.
Different actions are taken depending on the severity of the fault. The protection
relay tries to eliminate the fault by restarting. After the fault is found to be
permanent, the protection relay stays in the internal fault mode. All other output
REC615 & RER615
Technical Manual
Unit
ms
ms
Internal fault indications have the highest priority on the LHMI. None of
the other LHMI indications can override the internal fault indication.
Step
Default
0=No fiber
1=RS485 2Wire
1
0
1
0
6=9600
Basic functions
Description
Fiber mode
Serial mode
CTS delay
RTS delay
Baudrate
57

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer615

Table of Contents