Restvtr Function Block - ABB RELION REC615 Technical Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

1MRS758755 C
Table 66: ULTVTR Output signals
Name
ALARM
WARNING
3.14.3.5
Settings
Table 67: ULTVTR Non group settings (Basic)
Parameter
Values (Range)
Primary voltage
0.100...440.000
Secondary voltage
60...210
VT connection
1=Wye
2=Delta
3=U12
4=UL1
Amplitude Corr A
0.9000 ... 1.1000
Amplitude Corr B
0.9000 ... 1.1000
Amplitude Corr C
0.9000 ... 1.1000
Division ratio
1000 ... 20000
Voltage input type
1=Voltage trafo
3=CVD sensor
Angle Corr A
-20.0000...20.0000
Angle Corr B
-20.0000...20.0000
Angle Corr C
-20.0000...20.0000
3.14.3.6
Monitored data
Monitored data is available in three locations.
• Monitoring > I/O status > Analog inputs
• Monitoring > IED status > SMV traffic
• Monitoring > IED status > SMV accuracy
3.14.4

RESTVTR function block

REC615 & RER615
Technical Manual
Type
BOOLEAN
BOOLEAN
Unit
Step
kV
0.001
V
1
0.0001
0.0001
0.0001
1
deg
0.0001
deg
0.0001
deg
0.0001
Description
Alarm
Warning
Default
Description
20.000
Primary rated voltage
100
Secondary rated voltage
2=Delta
Voltage transducer measure-
ment connection
1.0000
Phase A Voltage phasor magni-
tude correction of an external
voltage transformer
1.0000
Phase B Voltage phasor magni-
tude correction of an external
voltage transformer
1.0000
Phase C Voltage phasor magni-
tude correction of an external
voltage transformer
10000
Voltage sensor division ratio
1=Voltage trafo Type of the voltage input
0.0000
Phase A Voltage phasor angle
correction of an external volt-
age transformer
0.0000
Phase B Voltage phasor angle
correction of an external volt-
age transformer
0.0000
Phase C Voltage phasor angle
correction of an external volt-
age transformer
Basic functions
117