General System Settings - ABB RELION REC615 Technical Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

Basic functions
3.1.11

General system settings

Table 18: General system settings
Parameter
Values (Range)
Rated frequency
1=50Hz
2=60Hz
Phase rotation
1=ABC
2=ACB
Blocking mode
1=Freeze timer
2=Block all
3=Block OPERATE
output
1
Bay name
IDMT Sat point
10...50
Frequency adaptivi-
0=Disable
ty
1=Enable
SMV Max Delay
0=1.90 1.58 ms
1=3.15 2.62 ms
2=4.40 3.67 ms
3=5.65 4.71 ms
4=6.90 5.75 ms
1
Used in the protection relay's main menu header and as part of the disturbance recording
identification
2
Depending on the product variant
48
Unit
Step
I/I>
1
1MRS758755 C
Default
Description
1=50Hz
Rated frequency of
the network
1=ABC
Phase rotation or-
der
1=Freeze timer
Behaviour for func-
tion BLOCK inputs
2
REC615
Bay name in system
50
Overcurrent IDMT
saturation point
0=Disable
Enabling frequency
adaptivity
1=3.15 2.62 ms
SMV Maximum al-
lowed delay
REC615 & RER615
Technical Manual