Non Group Settings - ABB RELION REC615 Technical Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

Basic functions
Parameter
Values (Range)
COT Length
1...2
IOA Length
1...3
Link Address
1...2
Length
ASDU Address
1...2
Length
Single Char Resp
0=False
1=True
Show Bad Time
0=False
1=True
Time Format
0=Short 24bit
1=Full 56bit
Event Time
0=Local
1=UTC
Overflow Mode
0=Oldest +indication
1=Keep newest
OvInd IOA
0...16777215
OvInd NoGI IOA
0...16777215
Event Order
0=Accurate time
1=Preserve chronology
Selection Timeout
1...65
Counter Reporting 0=Read by master
1=Spontaneous
Freeze mode
0=Not in use t
1=Freeze only
2=Freeze and Reset
TX window (k)
1...20
RX window (w)
1...20
TX timeout (t1)
1...60000
RX timeout (t2)
1...60000
Test interval (t3)
1...60000
Cyclical Period
1...604800
IT_FRZ
0=False
1=True
Inverted DIR bit
0=False
1=True
50
Unit
Step
Default
1
1
1
2
1
1
1
1
0=False
1=True
1=Full 56bit
1=UTC
0=Oldest +in-
dication
1
60000
1
60000
0=Accurate
time
s
1
30
0=Read by
master
0=Not in use
1
12
1
8
ms
1
30000
ms
1
10000
ms
1
20000
1
10
0=False
0=False
1MRS758755 C
Description
Cause of transmission length
Information Object Address length
Link Address Length
ASDU Address Length
Single character response enabled/ disa-
bled
Enable/disable bad time quality indica-
tion in events
Time stamp format 3 or 7 octet
Selects between UTC/Local time
Event buffer overflow handling mecha-
nism
Overflow indication address for interro-
gated data
Overflow indication address for non- in-
terrogated data
Selects the event ordering principle
Selection timeout for control SBO opera-
tions
Counter reporting after freeze
Periodic freezing mode for integrated to-
tals
IEC60870-5-104 transmit window (k)
IEC60870-5-104 receive window (w)
IEC60870-5-104 transmit timeout (t1)
IEC60870-5-104 receive timeout (t1)
IEC60870-5-104 link test interval (t3)
Cyclical period in seconds
Control point for freezing integrated to-
tals
Special mode for masters that require in-
verted DIR bit on Balanced IEC101 line.
If enabled, this protocol instance will be
non-compliant with the IEC 60870-5-101
standard.
REC615 & RER615
Technical Manual