1MRS758755 C
EFPADM Monitored data
Table 385: EFPADM Monitored data
Name
START_DUR
FAULT_DIR
COND_RES
SUS_RES
EFPADM
4.2.4.10
Technical data
Table 386: EFPADM Technical data
Characteristic
1
Operation accuracy
2
Start time
Reset time
Operate time accuracy
Suppression of harmonics
4.2.5

Harmonics-based earth-fault protection HAEFPTOC

1
Uo = 1.0 × Un
2
Includes the delay of the signal output contact, results based on statistical distribution of 1000
measurements
REC615 & RER615
Technical Manual
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
0=unknown
1=forward
2=backward
3=both
FLOAT32
-1000.00...1000.0
0
FLOAT32
-1000.00...1000.0
0
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
At the frequency f = f
±1.0% or ±0.01 mS
(In range of 0.5...100 mS)
Minimum
56 ms
40 ms
±1.0% of the set value of ±20 ms
-50 dB at f = n × f
Protection functions
Unit
Description
%
Ratio of start
time / operate
time
Detected fault
direction
mS
Real part of cal-
culated neutral
admittance
mS
Imaginary part
of calculated
neutral admit-
tance
Status
n
Typical
Maximum
60 ms
64 ms
, where n = 2, 3, 4, 5,...
n