Basic functions
Fault indication
Internal Fault
Card error,X130
Internal Fault
LHMI module
Internal Fault
RAM error
Internal Fault
ROM error
Internal Fault
EEPROM error
Internal Fault
FPGA error
Internal Fault
RTC error
Internal Fault
RTD card error,X130
Internal Fault
COM card error
For further information on internal fault indications, see the operation manual.
3.2.2

Warnings

In case of a warning, the protection relay continues to operate except for those
protection functions possibly affected by the fault, and the green Ready LED
remains lit as during normal operation.
Warnings are indicated with the text Warning additionally provided with the name
of the warning, a numeric code and the date and time on the LHMI. The warning
indication message can be manually cleared.
Table 26: Warning indications and codes
Warning indication
Warning
Table continues on the next page
60
Fault code Additional information
76
79
80
81
82
83
84
96
116
If a warning appears, record the name and code so that it can be
provided to ABB customer service.
Card in slot X130 is faulty.
LHMI module is faulty. The fault indication
may not be seen on the LHMI during the
fault.
Error in the RAM memory on the CPU card.
Error in the ROM memory on the CPU card.
Error in the EEPROM memory on the CPU
card.
Error in the FPGA on the CPU card.
Error in the RTC on the CPU card.
RTD card located in slot X130 may have per-
manent fault. Temporary error has occurred
too many times within a short time.
Error in the COM card.
Warning code
Additional information
10
A watchdog reset has occurred.
1MRS758755 C
REC615 & RER615
Technical Manual