Energizing Inputs Of Sim0002/Sim0904; Binary Inputs; Signal Output With High Make And Carry - ABB RELION REC615 Technical Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

1MRS758755 C
14.5

Energizing inputs of SIM0002/SIM0904

Table 755: Energizing inputs of SIM0002/SIM0904
Description
Current sensor in-
put
Voltage sensor in-
put
14.6

Binary inputs

Table 756: Binary inputs
Description
Operating range
Rated voltage
Current drain
Power consumption
Threshold voltage
Reaction time
1
Equals the current range of 40...4000 A with a 80 A, 3 mV/Hz Rogowski
2
Depending on the used nominal current (hardware gain)
3
This range is covered (up to 2*rated) with sensor division ratio of 10 000:1
REC615 & RER615
Technical Manual
Rated current voltage (in secon-
dary side)
Continuous voltage withstand
Input impedance at 50/60 Hz
Rated voltage
Continuous voltage withstand
Input impedance at 50/60 Hz
Value
±20% of the rated voltage
24...250 V DC
1.6...1.9 mA
31.0...570.0 mW
16...176 V DC
3 ms
Technical data
Value
1
75 mV...9000 mV
125 V
2
2...3 MΩ
3
6 kV...30 kV
50 V
3 MΩ
853

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer615

Table of Contents