Settings - ABB RELION REC615 Technical Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

1MRS758755 C
5.2.6.1
Table 518: CCBRBRF Input signals
Name
I_A
I_B
I_C
Io
BLOCK
START
POSCLOSE
CB_FAULT
5.2.6.2
CCBRBRF Output signals
Table 519: CCBRBRF Output signals
Name
CB_FAULT_AL
TRBU
TRRET
5.2.7

Settings

5.2.7.1
CCBRBRF Non group settings
Table 520: CCBRBRF Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Current value
0.05...2.00
Current value Res
0.05...2.00
CB failure trip
1=2 out of 4
mode
2=1 out of 3
3=1 out of 4
CB failure mode
1=Current
2=Breaker status
3=Both
CB fail retrip mode
1=Off
Table continues on the next page
REC615 & RER615
Technical Manual
Type
SIGNAL
SIGNAL
SIGNAL
SIGNAL
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
xIn
0.01
xIn
0.01
Protection related functions
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Residual current
0=False
Block CBFP operation
0=False
CBFP start command
0=False
CB in closed position
0=False
CB faulty and unable
to trip
Description
Delayed CB failure alarm
Backup trip
Retrip
Default
1=on
0.30
0.30
2=1 out of 3
1=Current
1=Off
Description
Operation Off / On
Operating phase
current
Operating residual
current
Backup trip current
check mode
Operating mode of
function
Operating mode of
retrip logic
489