Setting Parameters, Zone 4 - ABB REL 501-C1 2.5 Technical Reference Manual

Line distance protection terminal
Table of Contents

Advertisement

1.12
66
Distance protection (ZM)
Path in local HMI: Settings/Functions/Groupn/Impedance/Zone1-3
Table 77:
Settings for the phase-to-phase measurement ZM1 - 3 (ZMn--) function
Parameter
Range
Operation PP
Off, On
X1PP
0.10-400.00
Step: 0.01
R1PP
0.10-400.00
Step: 0.01
RFPP
0.10-400.00
Step: 0.01
Timer t1PP
Off, On
Timer t2PP
Timer t3PP
t1PP
0.000 -
60.000
t2PP
Step: 0.001
t3PP

Setting parameters, zone 4

Path in local HMI: Settings/Functions/Groupn/Impedance/Zone4
Table 78:
General zone setting parameters ZM4 (ZMn--) function
Parameter
Range
Operation
Off, NoneDir,
Forward,
Reverse
Path in local HMI: Settings/Functions/Groupn/Impedance/Zone4
Table 79:
Settings for the phase-to-phase measurement ZM4 (ZMn--) function
Parameter
Range
Operation PP
Off, On
Unit
Default
Description
-
Off
Operating mode for ZMn function for
Ph-Ph faults
ohm/ph
10.00
Positive sequence reactive reach of dis-
tance protection zone n for Ph-Ph faults
ohm/ph
10.00
Positive sequence line resistance
included in distance protection zone n for
Ph-Ph faults
ohm/loop
10.00
Resistive reach of distance protection
zone n for Ph-Ph faults
-
Off
Operating mode of time delayed trip for
the distance protection zone n for Ph-Ph
faults
s
0.000
Time delayed trip operation of the dis-
tance protection zone n for Ph-Ph faults
Default
Unit
Description
Off
-
Operating mode and directionality for
ZM4
Default
Unit
Description
Off
-
Operating mode for ZM4 for Ph-Ph faults
Chapter 4
Line distance