Supervision of AC input quantities (DA)
Parameter
Range
EnAlarms
Off, On
HiAlarm
0.0-9999.9
Step: 0.1
HiWarn
0.0-9999.9
Step: 0.1
LowWarn
0.0-9999.9
Step: 0.1
LowAlarm
0.0-9999.9
Step: 0.1
RepInt
0-3600
Step: 1
EnDeadB
Off, On
DeadBand
0.0-9999.9
Step: 0.1
EnIDeadB
Off, On
IDeadB
0.0-9999.9
Step: 0.1
EnDeadBP
Off, On
Operation
Off, On
Hysteres
0.0-99.9
Step: 0.1
EnAlRem
Off, On
EnAlarms
Off, On
HiAlarm
0.0-99.9
Step: 0.1
HiWarn
0.0-99.9
Step: 0.1
LowWarn
0.0-99.9
Step: 0.1
LowAlarm
0.0-99.9
Step: 0.1
Default
Unit
Description
Off
-
Set to 'On' to activate alarm supervision for
Q (produces an immediate event at opera-
tion of any alarm monitoring element, when
On)
300.0
Mvar
High Alarm level for Q
200.0
Mvar
High Warning level for Q
80.0
Mvar
Low Warning level for Q
50.0
Mvar
Low Alarm level for Q
0
s
Time between reports for Q in seconds. Zero
= Off (duration of time interval between two
reports at periodic reporting function. Setting
to 0 disables the periodic reporting)
Off
-
Enable amplitude dead band supervision for
Q
1.0
Mvar
Amplitude dead band for Q
Off
-
Enable integrating dead band supervision for
Q
10.0
Mvar
Integrating dead band for Q
Off
-
Enable periodic dead band reporting Q
Frequency measuring channel f: DA15-
Off
-
Operating mode for DAnn function
1.0
Hz
Alarm hysteresis for f
On
-
Immediate event when an alarm is disabled
for f (produces an immediate event at reset
of any alarm monitoring element, when On)
Off
-
Set to 'On' to activate alarm supervision for f
(produces an immediate event at operation
of any alarm monitoring element, when On)
55.0
Hz
High Alarm level for f
53.0
Hz
High Warning level for f
47.0
Hz
Low Warning level for f
45.0
Hz
Low Alarm level for f
Chapter 11