Setting Parameters; Technical Data - ABB REL 501-C1 2.5 Technical Reference Manual

Line distance protection terminal
Table of Contents

Advertisement

6.13.1
6.14
52
Configurable logic blocks (CL1)
Table 63:
Output signals for the TS (TSnn-) function block
Signal
ON
OFF

Setting parameters

Path in local HMI: Settings/Functions/Group1/TimerSet1/TimerSetnn
Table 64:
Setting parameters for the TS (TSn-) function
Parameter
Range
Operation
Off/On
T
0.00-60.00
Step: 0.01

Technical data

Table 65:
CL1 - Configurable blocks as basic
Update rate
Block
10 ms
AND
OR
INV
SM
GT
TS
200 ms
SR
XOR
Table 66:
Available timer function blocks as basic
Block
Availability
TM
10 timers
TP
10 pulse timers
TL
10 timers
TQ
10 puls timers
Description
Output from timer, pick-up delayed
Output from timer, drop-out delayed
Default
Unit
Description
Off
-
Operating mode for TSn function
0.00
s
Delay for settable timer n
Availability
30 gates
60 gates
20 inverters
20 flip-flops
5 gates
5 timers
5 flip-flops
39 gates
Setting range
0.000-60.000 s in steps
of 1 ms
0.000-60.000 s in steps
of 1 ms
0.0-90000.0 s in steps of
0.1 s
0.0-90000.0 s in steps of
0.1 s
Chapter 3
Common functions
Accuracy
± 0.5% ± 10 ms
± 0.5% ± 10 ms
± 0.5% ± 10 ms
± 0.5% ± 10 ms