2.6
High speed binary output logic (HSBO)

Setting parameters

Table 159: Setting parameters for the high speed binary output logic HSBO (HSBO-) func-
tion
Parameter
Range
IOMOD
0-13
TR1L1OUT
0-24
TR2L1OUT
0-24
TR1L2OUT
0-24
TR2L2OUT
0-24
TR1L3OUT
0-24
TR2L3OUT
0-24
CSL1OUT
0-24
CSL2OUT
0-24
CSL3OUT
0-24
CSMPHOUT
0-24
Default
Unit
Description
0
-
I/O module number for the fast output trip
contacts. Can only be set from the CAP
540 configuration tool.
0
-
Fast trip phase L1 output contact on I/O
module according to IOMOD setting. Can
only be set from the CAP 540 configura-
tion tool.
0
-
Fast trip phase L1 output contact on I/O
module according to IOMOD setting. Can
only be set from the CAP 540 configura-
tion tool.
0
-
Fast trip phase L2 output contact on I/O
module according to IOMOD setting. Can
only be set from the CAP 540 configura-
tion tool.
0
-
Fast trip phase L2 output contact on I/O
module according to IOMOD setting. Can
only be set from the CAP 540 configura-
tion tool.
0
-
Fast trip phase L3 output contact on I/O
module according to IOMOD setting. Can
only be set from the CAP 540 configura-
tion tool.
0
-
Fast trip phase L3 output contact on I/O
module according to IOMOD setting. Can
only be set from the CAP 540 configura-
tion tool.
0
-
Carrier send phase L1 output contact on
I/O module according to IOMOD setting.
Can only be set from the CAP 540 config-
uration tool.
0
-
Carrier send phase L2 output contact on
I/O module according to IOMOD setting.
Can only be set from the CAP 540 config-
uration tool.
0
-
Carrier send phase L3 output contact on
I/O module according to IOMOD setting.
Can only be set from the CAP 540 config-
uration tool.
0
-
Carrier send multiple phase output con-
tact on I/O module according to IOMOD
setting. Can only be set from the CAP
540 configuration tool.
Chapter 10
Logic
157