ABB REL 501-C1 2.5 Technical Reference Manual page 188

Line distance protection terminal
Table of Contents

Advertisement

176
Supervision of AC input quantities (DA)
Parameter
Range
Operation
Off, On
Hysteres
0.0-9999.9
Step. 0.1
EnAlRem
Off, On
EnAlarms
Off, On
HiAlarm
0.0-9999.9
Step: 0.1
HiWarn
0.0-9999.9
Step: 0.1
LowWarn
0.0-9999.9
Step: 0.1
LowAlarm
0.0-9999.9
Step: 0.1
RepInt
0-3600
Step: 1
EnDeadB
Off, On
DeadBand
0.0-9999.9
Step: 0.1
EnIDeadB
Off, On
IDeadB
0.0-9999.9
Step: 0.1
EnDeadBP
Off, On
Operation
Off, On
Hysteres
0.0-9999.9
Step: 0.1
EnAlRem
Off, On
Default
Unit
Description
Active power measuring channel P:
DA13-
Off
-
Operating mode for DAnn function
5.0
MW
Alarm hysteresis for P
On
-
Immediate event when an alarm is disabled
for P (produces an immediate event at reset
of any alarm monitoring element, when On)
Off
-
Set to 'On' to activate alarm supervision for P
(produces an immediate event at operation
of any alarm monitoring element, when On)
300.0
MW
High Alarm level for P
200.0
MW
High Warning level for P
80.0
MW
Low Warning level for P
50.0
MW
Low Alarm level for P
0
s
Time between reports for P in seconds. Zero
= Off (duration of time interval between two
reports at periodic reporting function. Setting
to 0 disables the periodic reporting)
Off
-
Enable amplitude dead band supervision for
P
1.0
MW
Amplitude dead band for P
Off
-
Enable integrating dead band supervision for
P
10.0
MW
Integrating dead band for P
Off
-
Enable periodic dead band reporting P
Reactive power measuring channel Q:
DA14-
Off
-
Operating mode for DAnn function
5.0
Mvar
Alarm hysteresis for Q
On
-
Immediate event when an alarm is disabled
for Q (produces an immediate event at reset
of any alarm monitoring element, when On)
Chapter 11
Monitoring