ABB REL 501-C1 2.5 Technical Reference Manual page 204

Line distance protection terminal
Table of Contents

Advertisement

192
Serial communication
Path in local HMI: Configuration/TerminalCOM/IECCom/Commands/ARBlock
Table 191: Setting parameters for controlling autorecloser command
Parameter
Range
Operation
On, Off
Path in local HMI: Configuration/TerminalCom/IECCom/Commands/ZCommBlock
Table 192: Configuration/TerminalCom/IECCom/Commands/ZCommBlock
Parameter
Range
Operation
On, Off
Path in local HMI: Configuration/TerminalCom/IECCom/Commands/LEDReset
Table 193: Setting parameter for controlling the LED reset command
Parameter
Range
Operation
On, Off
Path in local HMI: Configuration/TerminalCom/IECCom/Commands/SettingGrpn where
n=1-4
Table 194: Setting parameter for controlling the active setting group n command. n=1-4
Parameter
Range
Operation
On, Off
Path in local HMI: Configuration/TerminalCom/IECCom/Measurands
Table 195: Setting parameter for measurand type
Parameter
Range
MeasurandType
3.1, 3.2, 3.3,
3,4, 9
Path in local HMI: Configuration/TerminalCom/IECCom/FunctionType
Default
Unit
Parameter description
Off
-
Operation mode of autorecloser com-
mand. On=Blocked, Off=Released
Default
Unit
Parameter description
Off
-
Operation mode of protection command.
On=Blocked, Off=Released
Default
Unit
Parameter description
Off
-
Operation mode of LED reset command.
On=Blocked, Off=Released
Default
Unit
Parameter description
Off
-
Operation mode of active setting group
command. On=Blocked, Off=Released
Default
Unit
Parameter description
3.1
-
Measurand types according to the stan-
dard
Chapter 12
Data communication